and so for motor operation it is positive and for generator operation negative.

Figure 7.29 shows how the active power varies with slip for a 1 MW induction machine. A convention has been chosen with the current flowing into the circuit and so the normal operating region for a generator is between O and A. At 1 MW generation (A) the slip is around —0.8 percent with the rotor rotating faster than the stator field. It may be seen that the maximum power that may be generated before the peak of the curve is reached is only some 1.3 MW. This is because the generator jXs jX